Hyundai N5000 AC Drive / Inverter

Share |

Medium voltage inverter Hyundai N5000. Variador e inversor de
frecuencia de media tension Hyundai heavy industries N5000

 Hyundai N5000 Inverter Drive. Features

    High Performance and Efficiency

    Power Factor: over 0.95

  • No requirements for power factor correction capacitor

    System Efficiency: over 96%

  • System efficiency is improved by connecting the power and motor without input-output filter and output transformer

    Clean Power Input

  • A clean input wave is achieved via a secondary phase-shifted transformer
  • Without a filter, N5000 meets the stringent harmonic requirements of IEEE-519 (1992)
  • Protects the other equipment from harmonic disturbance

    Supplies of Clean Power for Motors

  • Output waveforms, without a filter, are close to sine waves due to multiple PWM control
    - No cable length & motor type restrictions
    - Existing motor can be used without modifications
    - Reduced noise and vibration of motors
    - 3.3kV - 13 level/6.6kV - 25 level output

    Small footprint and economical maintenance

  • Small footprint and reduced installation costs due to no requirements for ancillary equipment such as input & output filter and the integral structure incorporating the input transformer and inverter panel
  • Thanks to the modular single-phase inverter of draw-out type, easy maintenance and time saving are achieved.

    Outstanding operation features by the improved sensorless vector control

  • Energy saving V/F control for the fluid load (Fan, Pump)
  • Inherent speed sensorless vector control of N5000
    - High starting torque operation
    - Control of current, speed and vibration of motor at the low speed range of light duty
    - Quick torque responsiveness and improved speed precision
    - Strong control regardless of motor specifications

    Functions for trip-free operation (Option)

    Improved Cell Bypass

  • In case of cell failure during operation, the faulty cell will be bypassed and the neutral point will be shifted (balance is restored through angle adjustment). 92% of the rated voltage can be output after the failure of one cell.

    Redundant Inverter Controller

  • If the master controller is out of service during operation, output is generated due to automatic switching to the slave controller

    Redundant Fiber-Optic Cable for CAN Communication

  • If there are problems with the optic cable during operation, an automatic switching to the standby reserve optical communication H/W is made

    Redundant Control Power

  • The redundant control power module is equipped with AC 440V and DC 120V and monitors the control power. In case of the failure of a control power module, an automatic switching to the reserve module is made

    Certification (Korea Electro-Technology Research Institute)

  • Performance Test: Harmonics, Power Factor & Control
  • Environmental Tests of Cell Inverter and Control Parts: Constant Temperature, Vibration, EMI/EMC

    Display

    Inverter Operation Status Display

  • Operation frequency, input-output voltage, output current
  • Input-output of external signals
  • Warning status

    Inverter Fault Display

  • Fault type
  • Time of Fault
  • Operating frequency at time of fault
  • Voltage and current at time of fault

    Optional User Friendly PC-based Console (Option)

  • Remote operation and monitoring via laptop or desktop
  • Easy parameter setting and monitoring
  • Multiple communication interfaces (RS-232, RS-485, MODBUS)
  • Custom-made MMI display and upgrade support